Cable OSP CAT 6A
https://cableadocobreyfibraoptica.blogspot.com/2022/11/cable-osp-cat-6a.html

Cable OSP de categoría 6A, 4 pares, F/UTP, sin gel
Cable horizontal de categoría 6A para instalaciones, con clasificación OSP, 4 pares, conductores de cobre sólido desnudo de 23 AWG, F/UTP – apantallado, sin gel
OSP-Planta Exterior, Cable Horizontal de Premisa, Ethernet hasta 10GBASE-T, Wi-Fi 6, Wi-Fi 5, PoE++, PoE+, PoE, Enivronamientos Ruidosos, HDBaseT, Cámaras IP
Construction Details
CONDUCTOR
| Tamaño | Tipo | Material | Numero de pares |
|---|---|---|---|
| 23 | Solido | BC – Cobre | 4 |
INSULATION
| Material | Código de Color |
|---|---|
| PO – Polioelefina | Blanco & Azul, Blanco & Naranja, Blanco & Verde, Blanco & Café |
OUTER SHIELD
| Tipo de cubierta | Material | Cubierta | Tipo de Cable |
|---|---|---|---|
| Tape | Bi-Laminado (Alum+Poly) | 100% | 26 AWG (7×34) TC |
OUTER JACKET
| Separador | Material | Diámetro | Ripcord |
|---|---|---|---|
Center Member (Patented T-Spline®), EquiBlock Barrier Technology |
PO – Polyolefin | 0.29 in (7.4 mm) | Si |
| Diametro de Cable General (Nominal) | 0.29 in (7.4 mm) |
|---|
Electrical Characteristics
ELECTRICALS
| Max. Conductor DCR | Max. Capacitance Unbalance |
|---|---|
| 82 Ohm/km (25 Ohm/1000ft) | 45 pF/100m |
DELAY
| Frequency | Max. Delay | Max. Delay Skew | Nom. Velocity of Prop. |
|---|---|---|---|
| 100 MHz | 537.6 ns/100m | 45 ns/100m | 68% |
HIGH FREQUENCY
| Frequency [MHz] | Max. Insertion Loss (Attenuation) [dB/100m] | Min. NEXT [dB] | Min. PSNEXT [dB] | Min. ACR [dB] | Min. PSACR [dB] | Min. ACRF (ELFEXT) [dB] | Min. PSACRF (PSELFEXT) [dB] | Min. RL (Return Loss) [dB] | Max./Min. Input Impedance (unFitted) | Max./Min. Fitted Impedance | Min. PSANEXT [dB] | Min. PSAACRF [dB] | Min. TCL [dB] | Min. ELTCTL [dB] |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 2.1 | 74.3 | 72.3 | 72.2 | 70.2 | 67.8 | 64.8 | 20.0 | 105 +/- 10 | 115 +/- 15 | 67.0 | 67.0 | 40.0 | 35.0 |
| 4 | 3.8 | 65.3 | 63.3 | 61.5 | 59.5 | 55.8 | 52.8 | 23.0 | 105 +/- 10 | 100 +/- 7 | 67.0 | 66.2 | 40.0 | 23.0 |
| 8 | 5.3 | 60.8 | 58.8 | 55.4 | 53.4 | 49.7 | 46.7 | 24.5 | 100 +/- 22 | 100 +/- 7 | 67.0 | 60.1 | 40.0 | 16.9 |
| 10 | 5.9 | 59.3 | 57.3 | 53.4 | 51.4 | 47.8 | 44.8 | 25.0 | 100 +/- 22 | 100 +/- 7 | 67.0 | 58.2 | 40.0 | 15.0 |
| 16 | 7.5 | 56.2 | 54.2 | 48.8 | 46.8 | 43.7 | 40.7 | 25.0 | 100 +/- 22 | 100 +/- 7 | 67.0 | 54.1 | 38.0 | 10.9 |
| 20 | 8.4 | 54.8 | 52.8 | 46.4 | 44.4 | 41.8 | 38.8 | 25.0 | 100 +/- 22 | 100 +/- 7 | 67.0 | 52.2 | 37.0 | 9.0 |
| 25 | 9.4 | 53.3 | 51.3 | 44.0 | 42.0 | 39.8 | 36.8 | 24.3 | 100 +/- 22 | 100 +/- 7 | 67.0 | 50.2 | 36.0 | 7.0 |
| 31.25 | 10.5 | 51.9 | 49.9 | 41.4 | 39.4 | 37.9 | 34.9 | 23.6 | 100 +/- 22 | 100 +/- 7 | 67.0 | 48.3 | 35.1 | 5.1 |
| 62.5 | 15.0 | 47.4 | 45.4 | 32.4 | 30.4 | 31.9 | 28.9 | 21.5 | 100 +/- 22 | 100 +/- 7 | 65.6 | 42.3 | 32.0 | |
| 100 | 19.1 | 44.3 | 42.3 | 25.2 | 23.2 | 27.8 | 24.8 | 20.1 | 100 +/- 22 | 100 +/- 7 | 62.5 | 38.2 | 30.0 | |
| 200 | 27.6 | 39.8 | 37.8 | 12.2 | 10.2 | 21.8 | 18.8 | 18.0 | 100 +/- 22 | 100 +/- 7 | 58.0 | 32.2 | 27.0 | |
| 250 | 31.1 | 38.3 | 36.3 | 7.3 | 5.3 | 19.8 | 16.8 | 17.3 | 100 +/- 32 | 100 +/- 7 | 56.5 | 30.2 | 26.0 | |
| 300 | 34.3 | 37.1 | 35.1 | 2.9 | 0.9 | 18.3 | 15.3 | 16.8 | 100 +/- 32 | 100 +/- 7 | 55.3 | 28.7 | 25.2 | |
| 350 | 37.2 | 36.1 | 34.1 | 16.9 | 13.9 | 16.3 | 100 +/- 32 | 100 +/- 7 | 54.3 | 27.3 | 24.6 | |||
| 400 | 40.1 | 35.3 | 33.3 | 15.8 | 12.8 | 15.9 | 100 +/- 32 | 100 +/- 7 | 53.5 | 26.2 | 24.0 | |||
| 450 | 42.7 | 34.5 | 32.5 | 14.7 | 11.7 | 15.5 | 100 +/- 32 | 100 +/- 7 | 52.7 | 25.1 | 23.5 | |||
| 500 | 45.3 | 33.8 | 31.8 | 13.8 | 10.8 | 15.2 | 100 +/- 32 | 100 +/- 7 | 52.0 | 24.2 | 23.0 |
VOLTAGE
| Voltage Rating |
|---|
| 300 V |
Mechanical Characteristics
TEMPERATURE
| Operating | Installation | Storage |
|---|---|---|
| -20°C To +70°C | 0°C To +60°C | -40°C To +75°C |
BEND RADIUS
| Installation Min. |
|---|
| 2.9 in (74 mm) |
| Max. Pull Tension | 25 lbs (11 kg) |
|---|---|
| Bulk Cable Weight | 33 lbs/1000ft (49 kg/km) |
Standards and Compliance
| Environmental Suitability | Outdoor – Water Exposure, Outdoor |
|---|---|
| IEEE Compliance | IEEE 802.3bt Type 1, Type 2, Type 3, Type 4 |
| Data Category | Category 6A |
| TIA/EIA Compliance | ANSI/TIA-568.2-D Category 6A |
| ISO/IEC Compliance | 11801 ed 2.2 (2011) Class EA |
| CENELEC Compliance | Segregation class according EN50174-2 = a |
Product Notes
| Notes | Electrical values are expected performance based on cable testing and representative performance within a typical Belden system. Print Includes Descending Footage/Meter Markings from Max. Put-Up Length to 0. Not Suitable for Direct Burial. Cable jacket system is specially designed to protect cable core. Cable contains no water-blocking tapes, gels, or powders. Install in accordance with all applicable electrical codes. Maintain jacket integrity throughout installation process. Do not allow water or fluids to penetrate jacket sheath or to enter ends of cable. Ensure ends of cable will be protected from water/fluids after installation. Belden recommends using an entrance demarcation point when transitioning inside buildings with OSP cables. The suggested transition point is the REVConnect core coupler, part number RVACPKUBK-S1. |
|---|
History
| Update and Revision | Revision Number: 0.15 Revision Date: 11-01-2022 |
|---|
Part Numbers
| Item # | Color | Putup Type | Length |
|---|---|---|---|
| DOSP6AF 0101000 | Black | Reel | 1,000 ft |